A code-compliant residential kitchen needs more dedicated circuits than almost any other room. This tool takes the list of appliances you are wiring and returns the minimum required circuits per NEC 210.52, with the conductor size and GFCI/AFCI protection for each, so nothing gets shared that the code says must be dedicated.
How it works
The list always starts with the two mandatory small-appliance circuits, then adds an individual circuit per built-in appliance:
always: 2 × 20 A small-appliance circuits (NEC 210.52(B), 12 AWG Cu)
+ each selected appliance → its own dedicated circuit
countertop receptacles → GFCI (210.8(A))
kitchen branch circuits → AFCI (210.12)
The two small-appliance circuits serve the countertop receptacles and may extend to the dining room, but they cannot carry lighting or feed the built-in appliances. Each fixed appliance — dishwasher, disposal, microwave, and an electric range — gets its own circuit sized to its nameplate.
Worked example
A full kitchen with refrigerator, dishwasher, garbage disposal, built-in microwave, and electric range requires:
| Circuit | Size | Wire | GFCI | AFCI |
|---|---|---|---|---|
| Small-appliance #1 | 20 A / 120 V | 12 AWG Cu | Yes | Yes |
| Small-appliance #2 | 20 A / 120 V | 12 AWG Cu | Yes | Yes |
| Refrigerator | 20 A / 120 V | 12 AWG Cu | No* | Yes |
| Dishwasher | 15–20 A / 120 V | 14–12 AWG Cu | Yes | Yes |
| Disposal | 15–20 A / 120 V | 14–12 AWG Cu | Yes | Yes |
| Microwave | 20 A / 120 V | 12 AWG Cu | No* | Yes |
| Electric range | 40–50 A / 240 V | 8–6 AWG Cu | No | Yes |
*GFCI is not universally required for dedicated refrigerator or microwave circuits in all NEC editions; verify against the edition adopted in your jurisdiction.
That is seven circuits total. Swap the electric range for gas and eliminate the 240 V range circuit — the gas igniter plugs into one of the small-appliance circuits.
Circuit-by-circuit code basis
Small-appliance circuits (210.52(B)): At least two 20 A circuits are required to serve countertop receptacles. They may also serve the dining room and pantry. They may not serve lighting or fixed appliances.
Refrigerator: Best practice and increasingly code-required in newer editions is an individual 15 or 20 A circuit. Some older installs share with a small-appliance circuit, but a dedicated circuit prevents nuisance trips from other loads.
Dishwasher (210.8(D)): Individual circuit recommended; GFCI required since the 2020 NEC. Typically 15 or 20 A based on nameplate.
Garbage disposal: Individual 15 or 20 A circuit is standard. May share with dishwasher in some older codes via a split outlet, but modern practice and most inspectors prefer separation.
Electric range (210.52(B)(2)): A range, cooktop, or wall oven rated at more than 1.75 kW gets its own individual circuit. In practice a 240 V circuit at 40 to 50 A on 8 or 6 AWG copper, sized to the nameplate, is typical.
AFCI scope in the kitchen
Section 210.12 of the 2020 NEC requires arc-fault circuit interrupter protection for all 120 V, 15 and 20 A branch circuits in dwelling-unit kitchens. This means practically every kitchen circuit except the 240 V range circuit needs AFCI protection. Combination AFCI breakers at the panel or dual-function AFCI/GFCI devices can satisfy both requirements on circuits that need both.
Always verify the adopted NEC edition and any local amendments, since AFCI and GFCI scope has expanded across recent code cycles, and confirm each appliance’s nameplate before final breaker and conductor selection.