Box Fill Calculator (NEC 314.16)

Sum conductor, device, clamp, and fitting equivalents to verify junction/outlet box fill

Tabulates the NEC 314.16(B) volume allowances for conductors, devices, equipment grounding conductors, internal clamps, and fixture studs in cubic inches, then compares the total to the box's listed volume. For electricians selecting device and junction boxes. It runs free in your browser on Gera Tools, with nothing uploaded.

Last updated Source: Gera Tools

How much volume does each conductor count as?

Each insulated conductor entering or passing through the box counts as one volume allowance from Table 314.16(B): 2.00 cubic inches for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG, and so on by gauge. A conductor that runs through unbroken still counts once.

Overfilling an electrical box damages insulation, makes terminations unreliable, and fails inspection. NEC 314.16(B) assigns a cubic-inch allowance to every item in the box; this tool sums them under the correct counting rules and checks the total against the box’s listed volume.

How it works

Each category gets a volume allowance, with clamps, studs, devices, and the grounding allowance all based on the largest conductor present:

conductors = count × allowance(conductor gauge)
devices    = device count × 2 × allowance(largest conductor)
clamps     = (any clamps ? 1 : 0) × allowance(largest conductor)
studs      = fitting count × allowance(largest conductor)
grounds    = (any EGC ? 1 : 0) × allowance(largest EGC)
required   = sum of the above

If the required fill is at or below the box’s listed volume the box is compliant; otherwise it is overfilled.

Volume allowances by conductor gauge (NEC Table 314.16(B))

AWGCubic inches per conductor
181.50
161.75
142.00
122.25
102.50
83.00
65.00

These are the allowances for insulated conductors entering or passing through the box. Remember that each conductor counts once regardless of whether it enters, leaves, or runs completely through (a pass-through still counts as one allowance for the box it passes through).

Worked example — a typical device box

Imagine a single-gang box with:

  • Six 12 AWG conductors (two 12/2 cables, one 12/3): 6 × 2.25 = 13.5 in³
  • One duplex receptacle (device): 2 × 2.25 = 4.5 in³
  • Internal cable clamps (present): 1 × 2.25 = 2.25 in³
  • One equipment grounding conductor (12 AWG): 1 × 2.25 = 2.25 in³

Required fill: 22.5 cubic inches

A standard 14-cubic-inch single-gang box would be heavily overfilled. Even an 18 in³ box falls short. A 25 in³ or 26 in³ box, or a two-gang 36 in³ box used as a device box, would comfortably accommodate this fill.

Common boxes and their listed volumes

Box typeApproximate listed volume
Single-gang 2×4 switch box, 2-1/4” deep12 in³
Single-gang 2×4 switch box, 2-3/4” deep14 in³
Standard 2×4 box, 3-1/2” deep21 in³
Old-work 2×3 box (20.5 series)18 in³
Two-gang box, 3-1/2” deep36 in³
4” square box, 1-1/2” deep21 in³
4” square box, 2-1/8” deep30.3 in³
4-11/16” square box, 2-1/8” deep42 in³
Octagon box, 1-1/2” deep15.5 in³

Listed volumes are marked on the box or available in manufacturer data. Never estimate volume from outside dimensions; wall thickness reduces internal space.

Tips for inspectors and electricians

  • When a box is overfilled, the solutions are: a deeper box of the same gang, a box extension ring (which adds its listed volume to the total), moving splices to a separate junction box, or reducing conductors in that location.
  • Pigtails that begin and end in the same box are not counted separately — they are already captured by the conductor that enters the box.
  • The grounding allowance covers all equipment grounding conductors collectively — not one per conductor. However, an isolated ground (IG) system adds one additional allowance beyond the standard EGC.