Working safely near energized equipment starts with knowing how close anyone may get. This tool returns the NFPA 70E shock-protection approach boundaries for a given AC system voltage, distinguishing what a qualified worker may cross from what an unqualified worker must stay outside of, so you can mark out a safe work zone before the job starts.
How it works
The tool matches your voltage to a band in NFPA 70E Table 130.4(D)(a) and returns three distances:
limited approach (movable conductor) → unqualified must stay outside
limited approach (fixed circuit part) → smaller, for non-swinging parts
restricted approach (qualified only) → innermost shock boundary
The limited approach boundary is the line for unqualified personnel; crossing it requires being a qualified person or being escorted by one. The restricted approach boundary is the inner line a qualified person may cross only with rated insulated PPE, insulated tools, and a documented energized-work plan.
Understanding the two approach boundaries
NFPA 70E defines shock protection in two concentric zones:
Limited approach boundary — The outer perimeter. Unqualified workers (people who are not trained in electrical hazard recognition) must remain outside this line unless escorted by a qualified person and wearing appropriate PPE. There are two limited-approach distances because a movable conductor — such as an overhead service drop that can swing in wind — creates a larger hazard zone than a fixed busbar that stays put.
Restricted approach boundary — The inner perimeter, for qualified workers only. Crossing it requires rated insulated gloves, insulated tools, and a completed energized electrical work permit (EEWP). Contact inside this zone with an energized part causes direct shock, so the standard expectation is that qualified workers always use PPE and insulated tools when within this distance.
Voltage examples and typical distances
| Nominal system voltage | Limited approach (fixed conductor) | Restricted approach |
|---|---|---|
| 120 V | 3 ft 6 in | Avoid contact |
| 480 V | 3 ft 6 in | 1 ft 0 in |
| 600 V | 3 ft 6 in | 1 ft 0 in |
| 4,160 V | 5 ft 0 in | 1 ft 5 in |
| 15,000 V | 5 ft 0 in | 2 ft 2 in |
These are illustrative values from NFPA 70E Table 130.4(D)(a); always use the current adopted edition for your jurisdiction and verify against a qualified hazard assessment.
Shock vs. arc flash: they are different boundaries
The distances this tool returns are shock approach boundaries only. They govern proximity to energized conductors to prevent direct electrical contact. The arc flash boundary is entirely separate — it is a calculated distance based on incident energy (in cal/cm²) and the fault clearing time of the upstream overcurrent device, and it is frequently larger than the shock boundaries at medium-voltage or high-fault-current systems. A complete electrical safety analysis requires both: a shock hazard analysis (this tool covers that portion) and an arc flash study performed by a qualified electrical engineer using the incident energy method or the tables in NFPA 70E.
The most important principle in NFPA 70E is that the preferred option is always to de-energize and verify absence of voltage before working. Energized work is justified only when it can be shown that de-energizing would create a greater hazard or is infeasible due to equipment design.