Service-entrance conductors carry the entire load of a building, so the NEC gives them specific sizing rules. For single-phase dwellings, NEC 310.12 grants an 83 percent allowance that accounts for load diversity; for everything else, NEC 230.42 requires sizing to the full calculated load. This calculator handles both paths and returns a compliant copper or aluminum conductor.
How it works
In dwelling mode the tool applies the 310.12 allowance:
required ampacity = 0.83 × service rating
In general mode it sizes directly to your calculated load per 230.42. In either case it scans NEC Table 310.16 at the 75 C column and returns the smallest conductor whose ampacity meets the requirement. The 75 C column is used because NEC 110.14(C) caps loading at the termination temperature rating, which is 75 C for typical service equipment.
Worked example
A 200 A single-phase dwelling service needs 0.83 × 200 = 166 A. The smallest 75 C copper conductor meeting that is 2/0 AWG at 175 A; in aluminum it is 4/0 AWG at 180 A. These match the conductors electricians routinely pull for a 200 A residential service.
Common service sizes and their conductor requirements
| Service rating | Dwelling method (83%) | Min. copper (75°C) | Min. aluminum (75°C) |
|---|---|---|---|
| 100 A | 83 A required | 4 AWG (95 A) | 2 AWG (90 A) |
| 150 A | 124.5 A required | 1 AWG (130 A) | 2/0 AWG (135 A) |
| 200 A | 166 A required | 2/0 AWG (175 A) | 4/0 AWG (180 A) |
| 320 A | 265.6 A required | 350 kcmil (310 A) | 600 kcmil (310 A) |
| 400 A | 332 A required | 600 kcmil (420 A) | 1000 kcmil (375 A) |
These values assume a 75°C termination rating and no ambient correction. Confirm against the current edition of NEC Table 310.16 and your jurisdiction’s amendments.
The 83 percent allowance explained
The dwelling 83% rule in NEC 310.12 reflects the reality that residential loads are highly diverse — the range, dryer, water heater, AC, and EV charger rarely all run simultaneously at rated load. Allowing 83% of the service rating as the sizing basis accounts for this natural demand diversity without requiring a detailed load calculation. It is limited to single-phase, 120/240 V dwelling services; commercial and three-phase installations must use the full calculated load per 230.42.
Why aluminum is common for service entrances
Aluminum conductors are significantly larger in diameter than copper for a given ampacity, but service-entrance runs are typically short (from the meter to the main breaker) and do not bend repeatedly. Aluminum’s lower cost-per-foot for large conductors makes it the material of choice for 200 A and larger services. Connections must be made to AL-CU rated lugs and must use anti-oxidant compound; aluminum-to-copper direct terminations require rated connectors.
Notes
Size the grounded neutral from the maximum unbalanced load per 250.24(C) and 220.61, and the grounding electrode conductor from Table 250.66 — these are not the same as the ungrounded conductor size. Apply ambient correction if the service conductors pass through hot attic or rooftop spaces, and always confirm your termination temperature ratings before finalizing. Verify compliance with the authority having jurisdiction before rough-in on any permit work.