NEC Table 310.16 is the most-used table in the code book, and carrying it in a pocket reference saves time on every install. This tool reproduces the full table from 14 AWG through 2000 kcmil for both copper and aluminum across all three temperature columns, and applies live ambient and bundling derates.
How it works
Each conductor size has three published ampacities, one per insulation rating. The usable ampacity after corrections is:
adjusted ampacity = table value × ambient factor × bundle factor
The ambient factor comes from NEC Table 310.15(B)(1) based on the conductor’s temperature rating, and the bundle factor from Table 310.15(C)(1) based on the count of current-carrying conductors:
≤3 conductors → 1.00 4–6 → 0.80
7–9 → 0.70 10–20 → 0.50
21–30 → 0.45 31–40 → 0.40
Worked example with derating
A 4/0 AWG copper THWN conductor at 75 °C carries 230 A at the base 30 °C ambient with three or fewer current-carrying conductors. Move it into a 40 °C ambient (a hot attic, for example) with six current-carrying conductors in the same conduit:
- Ambient correction factor for 75 °C insulation at 40 °C: approximately 0.88
- Bundle adjustment for six conductors: 0.80
- Adjusted ampacity: 230 × 0.88 × 0.80 ≈ 162 A
That is nearly 30% less than the table value. Ignoring derating factors is one of the most common sizing errors in residential and commercial work.
Choosing the right temperature column
The three temperature columns in 310.16 correspond to insulation classes:
| Column | Insulation types | When to use |
|---|---|---|
| 60 °C | TW, UF | Rarely for new work; wet or damp locations |
| 75 °C | THW, THWN, RHW | Most commercial and industrial wiring |
| 90 °C | THHN, XHHW-2, RHH | Starting point for derating; often limited by terminals |
The practical rule: use 75 °C for most termination-limited circuits (equipment rated 60 °C for 100 A and below; 75 °C above 100 A per NEC 110.14(C)). You may use the 90 °C column as the base value for derating calculations, but if the derated result would exceed the 75 °C column value for that size, you are still limited by the terminal rating. In practice, THHN in conduit is almost always evaluated against the 75 °C column at the termination point.
Why aluminum has no entries below 12 AWG
Table 310.16 does not publish ampacities for aluminum conductors smaller than 12 AWG because such conductors are not used in practice for wiring — aluminum expands and contracts more than copper, and the terminations on small devices are not designed for it. The tool displays a dash for these blank entries rather than interpolating a value.
Notes
Always remember that the final breaker and lug termination rating still caps the result: a 75 °C-rated termination limits you to the 75 °C column no matter how the conductor is insulated. Verify against the adopted NEC edition in your jurisdiction, since ampacity tables have been revised across code cycles.