Multifamily Dwelling Load Calculation (NEC 220.84)

Size service for apartment buildings using NEC 220.84 optional demand factors

Applies NEC 220.84 optional-method demand factors to the total connected load across all dwelling units to calculate the minimum service ampacity for apartment, condo, and multifamily buildings. Runs in your browser. It runs free in your browser on Gera Tools, with nothing uploaded.

Last updated Source: Gera Tools

When can I use the NEC 220.84 optional method?

The optional method is permitted only when there are three or more dwelling units, every unit is equipped with electric cooking, and every unit has electric space heating, electric air conditioning, or both. If any of these is missing, you must use the standard method in 220.42 through 220.55.

Sizing the electrical service for an apartment or condo building one unit at a time wildly overshoots, because not every unit peaks at the same moment. NEC 220.84 gives a legal shortcut: sum the full connected load of every unit, then multiply by a single diversity factor from Table 220.84 that shrinks as the building grows.

How it works

The optional method first builds the connected load of one representative unit, then scales it to the whole building and applies the table factor:

per unit  = 3 VA/ft² × area
          + 1500 VA × small-appliance circuits (min 2)
          + 1500 VA laundry
          + range nameplate
          + larger of (A/C, heating)
          + other appliance nameplate
total     = per unit × number of units
demand VA = total × Table 220.84 factor
amps      = demand VA / service voltage

The demand factor starts at 45 percent for 3 to 5 units and falls step by step to about 28 percent for 40 or more units. Below 3 units the optional method is not allowed and no factor may be applied.

Example and notes

An 8-unit building of 900 ft² units, each with a 12 kVA range, 9 kVA electric heat, 5 kVA A/C, and 4.5 kVA of other appliances, has a per-unit connected load near 33 kVA. Across 8 units that is about 264 kVA, and the 42 percent factor for 8 units brings the demand to roughly 111 kVA, or about 462 A at 240 V — round up to a 600 A service. Always confirm each unit truly has electric cooking plus heating or cooling before relying on this method, and compare against the standard method if any unit is gas-fired.

Demand factor table (NEC Table 220.84)

The demand factor decreases as the building grows, because statistical diversity means fewer units peak simultaneously:

Number of unitsDemand factor
3 – 545%
6 – 744%
8 – 1043%
11 – 1342%
14 – 1541%
16 – 1740%
18 – 2039%
21 – 2238%
23 – 2537%
26 – 2736%
28 – 3035%
31 – 4034%
41 – 5033%
51 – 6032%
61 +28%

These figures match the percentages in NEC 2023 Table 220.84. At very large scale (61+ units) the factor stabilizes near 28%, reflecting the high diversity of a large apartment community.

Common pitfalls when using the optional method

Missing the eligibility check. The optional method is only valid when all three qualifying conditions hold: three or more units, electric cooking in every unit, and electric heating or cooling (or both) in every unit. If even one unit has gas cooking or no air conditioning, the optional method does not apply and you must use the standard method.

Using nameplate instead of calculated load. The range load entered should be the nameplate demand rating per NEC 220.55 or the calculated 8 kVA minimum for a single range. For cooking equipment rated above 1.75 kW, use the full nameplate. Do not estimate or round down nameplate kVA to save service amps.

Forgetting laundry. Each unit must include a 1500 VA laundry circuit. In a building with central laundry rather than in-unit hookups, consult 220.84 and local interpretation — some inspectors still require the per-unit laundry load, while others allow it to be replaced by the central laundry equipment load on a separate feeder.