kVA to Amps Converter

Convert kilovolt-amperes to amps for single-phase, split-phase, and three-phase systems

Convert transformer or generator kVA to line current in amps for single-phase and three-phase systems at any standard voltage (120, 208, 240, 277, 480, 600 V) using I = kVA × 1000 / V or I = kVA × 1000 / (√3 × V). It runs free in your browser on Gera Tools, with nothing uploaded.

Last updated Source: Gera Tools

What is the kVA to amps formula?

For single-phase, I = kVA × 1000 ÷ V. For three-phase, I = kVA × 1000 ÷ (√3 × V), where √3 ≈ 1.732 and V is the line-to-line voltage.

Reading a transformer nameplate in amps

Transformers, generators, and UPS units are rated in kVA — apparent power — but electricians need amps to size conductors, breakers, and disconnects. The conversion depends only on the kVA and the voltage, never on power factor, because kVA already bundles the real and reactive components together. This converter handles single-phase and three-phase systems at all the common North American voltages and shows the exact formula it used so you can check the work.

How it works

For a single-phase (or split-phase line-to-line) system the line current is:

I = kVA × 1000 / V

For a balanced three-phase system the apparent power is √3 × V × I, so solving for current gives:

I = kVA × 1000 / (√3 × V)

with V always the line-to-line voltage and √3 ≈ 1.732. Because three-phase spreads the same apparent power across three conductors, the same kVA at the same voltage produces a noticeably lower per-line current than single-phase would.

Common voltages and what they imply

SystemTypical voltageNotes
Single-phase residential120 V or 240 V240 V = line-to-line on a split-phase 120/240 panel
Light commercial three-phase208 VDelta or wye from a 120/208 V distribution transformer
Commercial three-phase480 VMost common industrial three-phase voltage in North America
High-voltage distribution600 VCanada and some industrial sites

For three-phase always enter the line-to-line voltage — not the line-to-neutral. The √3 factor in the formula already accounts for the 30-degree phase relationship between conductors, so using line-to-neutral would double-count it and give an inflated current that is wrong by a factor of √3.

Worked example

A 75 kVA three-phase transformer at 480 V has a full-load current of 75 × 1000 ÷ (1.732 × 480) ≈ 90.2 A. The same 75 kVA single-phase at 240 V would draw 312.5 A — over three times as much — which is exactly why distribution uses three-phase at higher voltage.

From full-load amps to breaker size

The tool gives you the full-load current (FLA), which is the starting point for protection sizing, not the final answer. The standard workflow from there:

  1. For continuous loads (loads energised for 3 hours or more), multiply FLA by 1.25 per NEC Article 215.
  2. Round up to the next standard overcurrent device (common sizes: 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 125, 150, 175, 200 A and larger).
  3. Verify conductor ampacity — check that the chosen wire gauge can carry the derated current at the installation temperature and accounting for any bundling derating.
  4. Compare against the transformer’s nameplate ampacity if listed; some nameplates already express FLA directly as a check.

The converter shows you step one. Steps two through four require the NEC tables and your specific installation conditions.