Most building departments want a load summary before they issue a residential electrical permit. This generator follows the NEC Article 220 standard calculation method: it sums general lighting, small-appliance, laundry, and fixed appliance loads, applies the demand factors, takes the larger of heating or cooling, and reports the calculated service amperes against your panel rating.
How it works
The standard dwelling method assembles the loads and applies a demand factor to the general portion:
general lighting = area_ft² × 3 VA
small appliance = 2 circuits × 1500 VA = 3000 VA
laundry = 1 circuit × 1500 VA
general subtotal = lighting + small appl + laundry
demand applied = 3000 VA at 100% + remainder at 35%
fixed appliances = range + dryer + water heater + other (nameplate VA)
hvac = larger of heating or A/C (220.60, non-coincident)
total VA = demand applied + fixed appliances + hvac
service amps = total VA / service voltage
The first 3000 VA of the general subtotal is counted in full, and everything above that is taken at 35 percent, which reflects that not all lighting and receptacle load runs at once.
Worked example
A 2000 square foot dwelling has 6000 VA of general lighting, plus 3000 VA small-appliance and 1500 VA laundry, for a 10,500 VA general subtotal. Applying the demand factor gives 3000 + (7500 × 0.35) = 5625 VA. Add an 8000 VA range, a 5000 VA dryer, a 4500 VA water heater, and a 6000 VA air conditioner (larger than the heat), for 29,125 VA total. At 240 volts that is about 121 amps, so a 150 amp service is the next standard size.
Understanding the demand factor
The 100%/35% split on the general subtotal is not arbitrary. NEC 220.42 codifies the observation that a home’s lighting and receptacle circuits are never all loaded simultaneously. Code requires the first 3000 VA in full because some base load is always present, but the rest is discounted to reflect diversity of use.
Fixed appliances like ranges and water heaters do not receive this discount because they are single loads that can run at or near nameplate. That is why a 10 kW electric range counts at full VA while thousands of square feet of lighting get derated.
Common errors on permit submissions
- Forgetting the two small-appliance circuits — NEC 210.11(C)(1) requires at least two 20 A circuits for kitchen receptacles; their 3000 VA must appear in the general subtotal regardless of what is actually plugged in.
- Using connected load instead of nameplate — enter the nameplate rating of the appliance, not an estimate of typical running load.
- Omitting the larger HVAC load — if both electric heat and central air are present, NEC 220.60 permits using only the larger non-coincident load, but you must still include it. Omitting HVAC entirely undersizes the service.
- Wrong voltage basis — single-phase 240 V services divide total VA by 240; confirm your service voltage before reading the calculated amps.
After the generator
Transfer the figures onto your AHJ’s official permit worksheet. Some jurisdictions use the optional calculation method under NEC 220.82 for new construction, which can result in a smaller service. The standard method used here is always conservative and always accepted. Keep the completed load summary with the permit set for inspection.