Temperature Correction Derating Calculator (NEC 310.15)

Derate conductor ampacity for ambient temperatures above 30 °C using NEC correction factors

Apply NEC Table 310.15(B)(1) ambient temperature correction factors to a base ampacity for 60 °C, 75 °C, and 90 °C insulation at ambients from 10 °C to 80 °C. Built for rooftop conduits, boiler rooms, and other hot installations. It runs free in your browser on Gera Tools, with nothing uploaded.

Last updated Source: Gera Tools

What ambient temperature counts?

Use the highest ambient the conductor is exposed to along its run, not the average. For conduit on a rooftop, the NEC adds a temperature adder for sun exposure, so the effective ambient can be far higher than the air temperature.

Why ambient heat shrinks a conductor’s rating

A conductor’s ampacity is the current it can carry without its insulation exceeding its rated temperature. The published value in NEC Table 310.16 assumes the surrounding air is at 30°C. When the ambient is hotter — a rooftop conduit baking in the sun, a boiler room, a packed equipment closet — there is less of a temperature gap for the conductor to dissipate its own heat into, so the same current would drive the insulation past its limit. The code handles this with a multiplier from Table 310.15(B)(1) that you apply to the base ampacity before sizing or loading the circuit.

How it works

The corrected ampacity is:

corrected = base_ampacity × temperature_factor

The factor depends on both the ambient temperature band and the insulation rating. At the 30°C basis the factor is exactly 1.0. Below 30°C it rises above 1.0 — cold air gives the conductor more headroom, so it can technically carry slightly more. Above 30°C it falls: a 75°C conductor at 46°C uses a factor of 0.82, so a 30 A base ampacity becomes about 24.6 A usable. The higher the insulation rating, the slower the factor falls, because the insulation can absorb more heat before it degrades.

The three insulation ratings compared

InsulationTypical wire typeFactor hits 0 near
60°CTW, UF~60°C ambient
75°CTHWN, XHHW~75°C ambient
90°CTHHN, XHHW-2~90°C ambient

The 90°C column is particularly important for rooftop and high-ambient installations: even though NEC typically limits termination loads to the 75°C column value, the 90°C column is the correct starting point when applying temperature correction factors. Specifying 90°C-rated wire and then using the 90°C correction factor often results in a conductor that still meets the 75°C termination limit after derating — a common design practice for hot locations.

Worked example

Take a 10 AWG copper THWN conductor (75°C rated) with a 35 A base ampacity. In a 50°C ambient, the NEC Table 310.15(B)(1) factor for 75°C insulation at that ambient band is 0.75:

corrected = 35 A × 0.75 = 26.25 A

That is a 28% reduction. If the circuit was sized at 30 A assuming full table ampacity, it is now overloaded and must be upsized or the conduit must be rerouted.

Rooftop conduit: the hidden temperature adder

NEC 310.15(B)(3)(c) adds a temperature correction to conduit on or above a rooftop based on the conduit’s height above the roof surface:

  • 0 to 7/8 inch above: add 33°C
  • 7/8 inch to 3.5 inches above: add 22°C
  • 3.5 inches to 12 inches above: add 17°C
  • Over 12 inches above: add 14°C

On a hot summer day where the air temperature reaches 40°C, conduit resting directly on a dark membrane roof could see an effective ambient of 73°C — well into the range where standard THWN has no usable ampacity. Always apply the adder before entering the ambient into this calculator.

Combining with other adjustment factors

Temperature derating and bundling derating (Table 310.15(C)(1)) are independent multipliers applied to the same base ampacity. The order does not change the result:

final_ampacity = base × temperature_factor × bundling_factor

Apply both whenever more than three current-carrying conductors share a raceway in a high-ambient location — it is one of the easiest ways to accidentally undersize wiring on a real installation.