The HVAC CFM airflow calculator turns a room’s heat load into the supply airflow you actually need to deliver. It uses the standard sensible-heat equation that every mechanical designer relies on to size diffusers, VAV boxes, and air-handler branches.
How it works
Required airflow comes from rearranging the two classic air-side heat equations:
sensible: Q_s = CFM x 1.08 x dT
latent: Q_l = CFM x 0.68 x d-grains
so:
CFM_sensible = Q_s / (1.08 x dT)
CFM_latent = Q_l / (0.68 x d-grains)
The constant 1.08 bundles standard air density, the specific heat of air, and the 60-minutes-per-hour conversion. The latent constant 0.68 does the same but for moisture removal, using the latent heat of vaporization and 7,000 grains per pound. You size the duct to whichever airflow is larger.
Worked example
A private office with a 12,000 BTU/h sensible cooling load and a 20 °F supply temperature difference:
CFM = 12,000 / (1.08 × 20) = 556 CFM
The same office has a 3,000 BTU/h latent load from occupants and a humidity-ratio difference of 25 grains/lb:
CFM = 3,000 / (0.68 × 25) = 176 CFM
The sensible requirement governs — design the branch for 556 CFM. If the latent load were the larger figure (common in high-occupancy spaces or humid climates), you would design to the latent airflow and check whether the coil can handle the sensible load at that higher airflow.
Choosing the right supply-air delta-T
The delta-T is a design choice, not a fixed constant. It affects diffuser selection, duct size, and occupant comfort:
| Delta-T (°F) | Effect |
|---|---|
| Less than 15 | High airflow, larger ducts, warmer supply, lower drafting risk |
| 18–22 | Typical comfort cooling range; 20 °F is the standard design default |
| More than 25 | Low airflow, smaller ducts, risk of cold drafts and condensation at diffusers |
A larger delta-T reduces the required CFM and lets you use smaller ducts — attractive for retrofits with limited ceiling depth. But pushing beyond 22–25 °F in occupied spaces risks “dumping” cold air that falls straight down from ceiling diffusers, creating uncomfortable drafts at head height. When in doubt, stay at 20 °F and size the diffuser for the resulting velocity.
Altitude correction
The constants 1.08 and 0.68 assume standard sea-level air density (0.075 lb/ft³). At altitude, air is less dense, so the same CFM carries less energy and the required airflow rises. At roughly 5,000 ft elevation, multiply the calculated CFM by approximately 1.20. Always apply a density correction for high-altitude projects — ignoring it undersizes the system.
For the most accurate altitude correction, calculate the actual air density at your project elevation and temperature, then substitute it into the heat equation in place of the standard 0.075 lb/ft³ factor. Published altitude correction factors assume a standard atmosphere, which may differ from actual site conditions if the climate is particularly hot or humid.